Possible Deviation From Specified Value During The Pressure Test (2 Of 11)
| Possible Deviation from Specified Value During the Pressure Test |
|---|
|
| Possible causes for the deviation from specified value and their solutions |
|
| Final Procedures |
| -- Charge the refrigerant circuit. Refer to REFRIGERANT CIRCUIT, CHARGING .-- Repeat the test. Refer to ELECTRICALLY-DRIVEN A/C COMPRESSOR, CHECKING PRESSURE WITH A/C SYSTEM SWITCHED ON . |
If too much refrigerant oil is located in the circuit, the A/C compressor must be discharges and replace the receiver/receiver/dryer (or dryer cartridge). Refer to Refrigerant Circuit . After cleaning the refrigerant circuit (flushing with refrigerant R1234yf) fill it with the correct quantity of refrigerant oil in the refrigerant circuit. Refer to REFRIGERANT CIRCUIT, CLEANING and Technical Data .
Check the measured values of the Evaporator Vent Temperature Sensor -G263- and the activation of the A/C compressor. If the measured value of the Evaporator Vent Temperature Sensor -G263- or the activation of the A/C compressor is faulty, the evaporator can freeze-up or the cooling output is not reached. Use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function for the A/C system and the battery regulation. Refer to Component Location Overview - A/C System and A/C Compressor .
With this malfunction, evaporator may ice up although the quantity of refrigerant in circuit is OK.
Likewise, the refrigerant circuit may become iced if there is a malfunction on the Evaporator Vent Temperature Sensor -G263- or/and on the temperature sensor after hybrid battery evaporator. For this concern also pay attention to the measured value of the Evaporator Vent Temperature Sensor -G263- and the temperature sensor after hybrid battery evaporator (on vehicles with battery cooling module). Use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function of the A/C system and the battery regulation. Refer to Component Location Overview - A/C System .