Possible Deviation From Specified Value During The Pressure Test (3 Of 11)
| Possible Deviation from Specified Value during the Pressure Test |
|---|
|
| Possible causes for the deviation from specified value and their solutions |
|
| Final Procedures |
| -- Charge the refrigerant circuit. Refer to REFRIGERANT CIRCUIT, CHARGING .-- Repeat the test. Refer to ELECTRICALLY-DRIVEN A/C COMPRESSOR, CHECKING PRESSURE WITH A/C SYSTEM SWITCHED ON . |
For the malfunction "high pressure normal, low pressure too low" With this malfunction, evaporator may ice up, although quantity of refrigerant in circuit is OK.
If there is a malfunction an the refrigerant circuit, it was not activated and operates nevertheless, it is not necessary to clean the refrigerant circuit (flush with refrigerant R1234yf). Refer to REFRIGERANT CIRCUIT, CLEANING . For this error it is sufficient to replace the A/C compressor (pay attention to the refrigerant oil quantity in the A/C compressor). Refer to COMPONENTS, REPLACING and A/C Compressor .
If there is a fault in the A/C compressor (the A/C compressor is activated by the A/C compressor control module at too high of a speed), it is not necessary to clean the refrigerant circuit (flushing with refrigerant R1234yf). For this malfunction it is sufficient to replace the A/C compressor (pay attention to the refrigerant oil quantity in the A/C compressor). Refer to REFRIGERANT CIRCUIT, CLEANING , Technical Data and A/C COMPRESSOR .
If the expansion valve (or one of the two expansion valves) is faulty (permanently closed or does not open sufficiently), the A/C compressor is also actuated to maximum output and the pressure on the low pressure side drops to specified value or below (compressor draws off refrigerant from the low-pressure side). Since the refrigerant cannot flow via the faulty expansion valve, the cooling output in the downstream evaporator is not attained and the high pressure may also not increase or only increase slightly due to the absence of energy. The A/C compressor may thereby be activated with a higher speed since the required cooling output is not attained in an evaporator. The same applies if the function or the activation of the refrigerant shut-off valve 1 or the refrigerant shut-off valve 2 is faulty. Use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function for the A/C system and the battery regulation. Refer to Refrigerant Circuit .
Check the measured values for the Evaporator Vent Temperature Sensor -G263- (and the measured values for the Temperature Sensor Before Hybrid Battery Evaporator -G756- and the Temperature Sensor After Hybrid Battery Evaporator -G757-) as well as the activation of the A/C compressor by the A/C Compressor Control Module --. If the measured value of the Evaporator Vent Temperature Sensor -G263- (the Temperature Sensor Before Hybrid Battery Evaporator -G756-, Temperature Sensor After Hybrid Battery Evaporator -G757-) or the activation of the A/C compressor is faulty, the evaporator can freeze up or the required cooling output is not read. Use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function for the A/C system and the battery regulation and refer to Component Location Overview - A/C System .