Possible Deviation From Specified Value During The Pressure Test (1 Of 11)
| Possible Deviation from Specified Value During the Pressure Test |
|---|
|
| Possible causes for the deviation from specified value and their solutions |
|
| Final Procedures |
| -- Charge the refrigerant circuit. Refer to REFRIGERANT CIRCUIT, CHARGING .-- Repeat the test. Refer to ELECTRICALLY-DRIVEN A/C COMPRESSOR, CHECKING PRESSURE WITH A/C SYSTEM SWITCHED ON . |
If for this complaint a malfunction is determined in the diagnostic, check the refrigerant circuit for a constriction or blockage (a constriction or a blockage in the refrigerant circuit can also lead to these complaints). If nothing is determined here, clean the refrigerant circuit (flush with refrigerant R1234yf). Refer to REFRIGERANT CIRCUIT, CLEANING .
Check the measured values of the sensors for Evaporator Vent Temperature Sensor -G263- and if equipped the temperature sensor before hybrid battery evaporator and the temperature sensor before hybrid battery evaporator as well at the activation of the A/C compressor via the corresponding control module. Use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function for the A/C system and the battery regulation.
If there is an error in the measured value of the Evaporator Vent Temperature Sensor -G263-, the temperature sensor before hybrid battery evaporator or the temperature sensor after hybrid battery evaporator (depending on the vehicle use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function for the A/C system and the battery regulation) this can lead to problems in the cooling output and the evaporator can freeze-up.
With a malfunction on one of the temperature sensors, the evaporator may ice up even though the quantity of refrigerant in the refrigerant circuit is OK.
If the A/C system function is not OK after repeating the test, for example after replacing expansion valve, clean the refrigerant circuit by flushing using the refrigerant R1234yf. Refer to REFRIGERANT CIRCUIT, CLEANING . Replace the A/C compressor and dryer cartridge (or reservoir/receiver/dryer). Refer to Refrigerant Circuit .
If the expansion valve in the heater and A/C unit evaporator or the shut-off valve is faulty (permanently closed or does not open sufficiently), the A/C compressor is actuated to maximum output and the low pressure drops to specification or below (compressor draws off refrigerant from low-pressure side). Since the refrigerant cannot flow via the expansion valve, the cooling output is not attained, high pressure may also not increase or only increase slightly due to the absence of energy. Use the Vehicle Diagnostic Tester in the"Guided Fault Finding" Function for the A/C System and the Battery Regulation. Refer to Refrigerant Circuit .
The evaporator in the heater and A/C Unit has considerably more output than the evaporator for battery cooling. The refrigerant shut-off valve 2 on the expansion valve in the battery cooling module depending on the version is activated for cooling the Electric Vehicle Battery -A2- (depending on the vehicle use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function of the A/C system and the battery regulation) first after a specific battery temperature by the corresponding control module (for example from the battery regulation control module) so that the energy transformation via the evaporator for battery cooling is not or only slightly raised. Use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function for the A/C system and the battery regulation. Refer to Refrigerant Circuit .