LEMON Manuals: Even more car manuals for everyone: 1960-2025
Home >> Audi >> 2021 >> A4 Quattro Premium Plus, 2.0L Eng VIN B >> Repair and Diagnosis >> Heating, Ventilation & A/C (HVAC) >> HVAC Control Systems >> Air Conditioning (Refrigerant R1234YF Servicing) (2 Of 2) >> 87 Air Conditioning >> Working With A/C Service Station >> Refrigerant Circuit, Evacuating >> Notes

Refrigerant Circuit, Evacuating: Notes

The refrigerant circuit must be evacuated before it is filled with refrigerant (vacuum). Moisture is also extracted by this from the circuit.

Leaks may be found when evacuating the refrigerant circuit. Refer to LEAKS, FINDING .

CAUTION:

Risk of damaging the A/C compressor by the refrigerant circuit vacuum.

- Never start the engine with vacuum in the refrigerant circuit.

Evacuating:

-- On vehicles with a high-voltage system, switch off (deactivate) the "auxiliary climate control" function. Refer to the Owner's Manual and Infotainment/MMI Operating Manual.

-- Switch off the ignition.

-- Connect the A/C service station to the power supply.

Additionally on vehicles with electric operated valves in the refrigerant circuit, which cannot be opened without power:

NOTE:

On vehicles with high-voltage system and additional functions of the A/C system ("heat pump operation" or "cooling the high-voltage battery") valves may be installed in the refrigerant circuit which cannot be opened without power. These valves are opened and closed for example via a step motor and after switching off the ignition are no longer activated. To completely discharge, correctly evacuate and charge the refrigerant circuit, no sections may be closed. Therefore these valves must be opened before performing this work. Refer to Refrigerant Circuit and use the Vehicle Diagnostic Tester in the"Guided Fault Finding"  function.

The check valves in the refrigerant circuit in the flow direction have a specified residual pressure (approximately 0.1 bar or 100 mbar (1.45 psi)). So that the refrigerant circuit can be completely evacuates (residual pressure less than 5 mbar (72.5 psi)) all electrically activated valves must be opened.

-- Open the electrically activated valves, which to now open without power using the Vehicle Diagnostic Tester in the"Guided Fault Finding"  function.

All Vehicles

-- Switch on the A/C service station and the related Owner's Manual according to specification. Refer to A/C service station Owner's Manual.

-- Remove the closure caps from the refrigerant circuit service connections. Refer to Refrigerant Circuit and the vehicle-specific refrigerant circuit.

-- Check the refrigerant circuit service connections of debris and corrosion and if necessary clean.

NOTE:

Dirt or a rough surface on the service connections due to corrosion can cause seal damage, which can then cause premature failure of the quick-release couplings.

-- Connect the A/C service station to the refrigerant circuit. Refer to A/C SERVICE STATION ON REFRIGERANT CIRCUIT, CONNECTING .

-- Switch on the A/C service station, evacuate the refrigerant and perform a pressure test (vacuum pump on for approximately 10 minutes to remove air, remaining refrigerant and moisture and 20 minute pressure/pressure increase test).

NOTE:

The pressure at the end of the evacuation process must be smaller than 5 bar (72.5 psi) absolute pressure (the vacuum pump of the A/C service station runs). If during the evacuation process the refrigerant circuit pressure is not smaller than 5 mbar (.07 psi), this may have various causes: For example leaks in the refrigerant circuit or in the connection to the A/C service station causes the evacuation time to be too short the vacuum pump from the A/C service station does not generate the required vacuum or the vacuum sensor from the A/C service station is not correctly calibrated. Refer to the A/C service station Owner's Manual.

An absolute pressure of 5 mbar (0.07 psi) corresponds to for example a absolute pressure of 980 mbar (14.21 psi) a vacuum of 975 mbar (14.14 psi).

At the end of the vacuum/pressure increase test the refrigerant circuit pressure must not be higher than 20 mbar (0.29 psi) absolute pressure. If the refrigerant circuit pressure during the vacuum/pressure increase test is greater than 20 mbar (0.29 psi), the vacuum pump is switched on and the procedure begins again. Refer to the A/C service station Owner's Manual. If after repeating the procedure twice the refrigerant circuit pressure does not stay smaller than 20 mbar (0.29 psi), this may have various causes. If there are leaks in the refrigerant circuit, leaks in the connection from the refrigerant circuit to the A/C service station or in the A/C service station itself, the time for the evacuation time is too short or the time for the vacuum/pressure increase is too long.

If it is suspected that a leak in the refrigerant circuit is present if necessary switch off the A/C service station and let it sit as long as possible (for example one hour to check for leaks in the refrigerant circuit). Refer to the A/C service station Owner's Manual.

Depending on the version of the A/C service station the refrigerant circuit pressure is displayed directly, it can also be the case that only when the vacuum pump is running the current pressure is shown. Refer to the A/C service station Owner's Manual. If the A/C service station only displays the ambient pressure then the display of the refrigerant circuit pressure is dependent on the ambient pressure when turning on (the ambient pressure at 980 mbar (14.21 psi) corresponds to a vacuum of 975 mbar (14.14 psi) a residual pressure of 5 mbar (0.07 psi) absolute pressure).

If the refrigerant circuit was opened, a small amount of moisture may have entered the refrigerant circuit. If this is the case, evacuate the refrigerant circuit for at least 30 minutes (refrigerant circuit pressure less than 20 mbar before filling).

If refrigerant was extracted (to check the capacity) and the refrigerant circuit is only evacuated to fill it again (the refrigerant circuit was not opened and has no leaks) it is enough to evacuate the refrigerant circuit for five minutes and no time or only a short amount of time (for example one minute) is needed adjust the vacuum/pressure increase test (no air and no moisture has entered the refrigerant circuit).

Depending on the quantity of refrigerant oil in the refrigerant circuit, the age and the mileage of the vehicle, the design of the refrigerant circuit etc. it can also be the case, that the specified absolute pressure in the refrigerant oil raises above the specified 20 mbar (0.29 psi) during the vacuum test. Due to refrigerant (and also due to moisture) which has evaporated from the refrigerant oil on a refrigerant circuit without leaks. If this is the case repeat again and/or adaptation the pre-set times accordingly.

If the vacuum reading does not change (and the pressure remains smaller than 20 mbar (0.29 psi)) the system does not have leaks and can be filled.

NOTE:

Depending on the version of the A/C service station the current refrigerant circuit pressure is constant or is displayed after switching of for evacuate the "Evacuate" function. Refer to the A/C service station Owner's Manual.

Because of the high temperature of the evacuation it can be the case that the refrigerant evaporating from the refrigerant oil can cause the refrigerant circuit pressure to increase during the vacuum test to 20 to 40 mbar (0.29 to 0.58 psi) (absolute pressure). This does not indicate a leak in the refrigerant circuit be depending on the version of the A/C service station can lead to a displayed malfunction. If necessary evacuate the refrigerant circuit again and monitor the vacuum indicator over a longer time, once the vacuum is maintained and it is ensured that there are no leaks in the refrigerant circuit, the system may be filled.

-- Charge the refrigerant circuit using the A/C service station. Refer to REFRIGERANT CIRCUIT, CHARGING .

If the vacuum is not maintained or cannot generate a sufficient vacuum, perform the following:

-- If it is possible that the refrigerant circuit may have leaks, evacuate and check the vacuum display again over several hours Only when the vacuum is maintained can the refrigerant circuit be charged.

-- It can only be filled once it is ensured that refrigerant circuit does not have leaks. Refer to REFRIGERANT CIRCUIT, CHARGING .