LEMON Manuals: Even more car manuals for everyone: 1960-2025
Home >> Audi >> 2021 >> A4 Quattro Premium Plus, 2.0L Eng VIN B >> Repair and Diagnosis >> Heating, Ventilation & A/C (HVAC) >> General Servicing >> Air Conditioning (Refrigerant R134A Servicing) (1 Of 2) >> 87 Air Conditioning >> Pressures, Checking >> Vehicles With RESTRICTOR, Receiver/Dryer And A/C Compressor Regulator Valve -N280-, Checking Pressures, Externally Regulated Compressor >> Specified Values For Refrigerant Circuit Pressures

Specified Values For Refrigerant Circuit Pressures

High-Pressure Side:

Increasing from initial pressure (when connecting the pressure gauges) to a maximum of 20 bar (290 psi).

Low Pressure:

Decreasing from initial pressure (when connecting pressure gauges) to the value in the graph.

Fig 1: Identifying Permissible Tolerance Range Graph
GWWA87-10582Courtesy of AUDI OF AMERICA, LLC

A -  Low pressure (measured at service connection) in bar (psi)

B -  Control current for A/C Compressor Regulator Valve -N280- in amps.

C -  Permissible tolerance range (applicable to compressor capacity utilization of 10 to 90%)

NOTE:

If high cooling output is needed (for example, the outside temperature is very high, the blower speed it set on high but the engine RPMs are low), then the A/C compressor will not bring the pressure on the low pressure side to the value specified in the diagram -C- (for example, for a certain time after turning on the A/C). The A/C compressor is actuated with maximum specified control current, however delivery volume is no longer sufficient at this engine speed to reduce pressure on low-pressure side to value in graph. To check the A/C compressor control under these conditions, for example, the fresh air blower is controlled only with approximately 40% of the maximum voltage, check the pressures at a lower fresh air blower speed. Use the Vehicle Diagnostic Tester ("OBD" or "Guided Fault Finding for the A/C system") and COOLING OUTPUT, CHECKING or Refrigerant Circuit .

Under unfavorable conditions (very high ambient temperatures, high humidity), pressure on high-pressure side may increase to max. 29 bar (421 psi).

Control current -B- is displayed in measured value block of A/C Control Head -E87- or control head, Climatronic Control Module -J255-.

The high pressure measured from the High Pressure Sensor -G65- (or the A/C Pressure/Temperature Sensor -G395- or the Refrigerant Circuit Pressure Sensor - G805-) is displayed as the measured value (by the Front A/C Display Control Head -E87-, the A/C Control Module -J301- or the display and control unit, and the A/C Control Module -J255-).

Low pressure settles depending on control current for A/C Compressor Regulator Valve -N280- and control characteristic of expansion valve within compressor output range in tolerance range.

Under unfavorable conditions (very high ambient temperatures, high humidity), compressor output may not always be sufficient to attain the specified value.

If compressor capacity utilization is greater than 90%, pressure on low-pressure side may be in excess of tolerance range "C" shown in graph (compressor output no longer sufficient).

The specified operating current for the A/C Compressor Regulator Valve -N280- must be greater than 0.3 A in order to ensure reliable regulator valve actuation.

In "maximum cooling output" setting, control current for A/C Compressor Regulator Valve -N280- is regulated to approximately 0.65 A (up to 0.85 A). This measured value is vehicle-specific and displayed in the measured value block.

At absolute pressure, 0 bar/psi corresponds to absolute vacuum. Normal ambient pressure corresponds to 1 bar (14.5 psi) absolute pressure. On the scales of most pressure gauges, 0 bar/psi corresponds to an absolute pressure of 1 bar (14.5 psi) (can be seen from -1 bar (-14.5 psi) mark below 0). Use the Vehicle Diagnostic Tester ("OBD" or "Guided Fault Finding for the A/C System") and COOLING OUTPUT, CHECKING or Refrigerant Circuit .

Possible Deviation from Specification Possible Cause of Fault Corrective Action
  • High pressure remains constant or increases only slightly (above pressure with engine stopped),
  • Low pressure quickly drops to value in graph or below
  • Required cooling output is not attained
  • Actuation of A/C Compressor Regulator Valve -N280- malfunctioning.
  • Not enough refrigerant in refrigerant circuit
  • Expansion valve faulty
-- Check the A/C Compressor Regulator Valve -N280- activation. Refer to Refrigerant Circuit .-- Extract refrigerant from the refrigerant circuit
  • If quantity of refrigerant extracted is substantially less than specified capacity:
  • High pressure normal
  • Low pressure in line with value in graph
  • Required cooling output is not attained
  -- Localize the leak with leak detector and eliminate-- Charge the refrigerant circuit.-- Repeat the test.
  • High pressure normal
  • Low pressure too low (see graph)
  • Required cooling output is not attained
 
  • If quantity of refrigerant extracted roughly corresponds to specified capacity:
-- Replace the expansion valve.-- Charge the refrigerant circuit.-- Repeat the test.
NOTE:

If no fault is found with this malfunction, clean the refrigerant circuit (flush using refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blow through using compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN .

Check the measured values from the Evaporator Vent Temperature Sensor -G263- and the A/C Compressor Regulator Valve -N280- control. If measured value of Evaporator Vent Temperature Sensor -G263- is not OK, evaporator may ice up or cooling output is not attained.

If air conditioner operation is not OK when test is repeated after replacing expansion valve, install old expansion valve, clean refrigerant circuit (flush using refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blow through using compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN . Then replace the A/C compressor and receiver/dryer.

With this malfunction, evaporator may ice up although the quantity of refrigerant in circuit is OK.

If the expansion valve is malfunctioning (permanently closed or does not open sufficiently), the A/C Compressor Regulator Valve -N280- is actuated to maximum output and low pressure drops to value in graph or below (compressor draws off refrigerant from low-pressure side). Since refrigerant cannot flow via expansion valve, cooling output is not attained, high pressure may also not increase or only increase slightly due to the absence of energy Vehicle Diagnostic Tester ("OBD" or "Guided Fault Finding for the A/C System") and COOLING OUTPUT, CHECKING or Refrigerant Circuit .

Possible Deviation from Specification Possible Cause of Fault Corrective Action
  • High pressure does not increase or only increases slightly above pressure with engine stopped.
  • Low pressure does not drop or drops only slightly.
  • Required cooling output is not attained
  • The A/C compressor is not activated (A/C Compressor Regulator Valve -N280-)
  • The A/C compressor is not being driven.
-- Check and service the A/C compressor activation and drive. Refer to A/C Compressor .
 
  • A/C Compressor Regulator Valve -N280- faulty
-- Check the A/C Compressor Regulator Valve -N280- functionality. If necessary, replace the valve A/C Compressor Regulator Valve -N280- and check for dirt. Refer to A/C Compressor Regulator Valve -N280-, REMOVING AND INSTALLING .
 
  • Constriction or obstruction in refrigerant circuit (for example, inside the refrigerant line between the service connection "low pressure side" and the A/C compressor).
-- Clean the refrigerant circuit (flush with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blow through with compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN ).-- Replace the hose or line if kinked or constricted.
 
  • A/C compressor faulty.
-- Replace the A/C compressor.
NOTE:

Make sure the A/C compressor (the A/C compressor shaft) is actually being driven by the belt pulley/drive unit. Refer to A/C Compressor .

As of MY 2012, certain engines and A/C compressors that in addition to the A/C Compressor Regulator Valve -N280-, have an A/C clutch -N25- attached to the belt pulley. Make sure the A/C Compressor Regulator Valve -N25- is indeed being actuated and the A/C compressor (A/C compressor shaft) is being driven by the belt pulley. Refer to A/C Compressor and to the Parts Information.

Possible Deviation from Specification Possible Cause of Fault Corrective Action
  • High pressure increases above specification
  • Low pressure quickly drops to value in graph
  • Required cooling output is not attained
  • Actuation of A/C Compressor Regulator Valve -N280- malfunctioning.
  • Constriction or obstruction in refrigerant circuit
  • Expansion valve faulty
-- Check the A/C Compressor Regulator Valve -N280- activation. Refer to Refrigerant Circuit .-- Run hand over refrigerant circuit to check for differences in temperature
  • If difference in temperature is found at one component:
-- Replace the hose or line if kinked or constricted.-- In the event of an obstruction, clean refrigerant circuit (flush with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blow through with compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN ).-- Charge the refrigerant circuit.-- Repeat the test.
  • If no malfunction can be found:
-- Clean the refrigerant circuit (flush with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blow through with compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN ).-- Charge the refrigerant circuit.-- Repeat the test if the function is not OK:-- Replace the expansion valve and receiver/dryer
NOTE:

If the function of the A/C system is not OK when the test is repeated, replace the expansion valve and receiver/dryer.

With this malfunction, evaporator may ice up although the quantity of refrigerant in circuit is OK.

If expansion valve is malfunctioning (permanently closed or does not open sufficiently), A/C Compressor Regulator Valve -N280- is actuated to maximum output and low pressure drops to value in graph or below (compressor draws off refrigerant from low-pressure side). Since refrigerant cannot flow via expansion valve, cooling output is not attained, high pressure may also not increase or only increase slightly due to the absence of energy. Use the Vehicle Diagnostic Tester ("OBD" or "Guided Fault Finding for the A/C System") and COOLING OUTPUT, CHECKING or Refrigerant Circuit .

If there is too much refrigerant oil in the circuit, the compressor must be drained and the receiver/dryer must be replaced. After cleaning the refrigerant circuit (flushing with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blowing through using compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN ), the correct quantity of refrigerant oil is filled into the circuit. Refer to REFRIGERANT R134A CAPACITIES, REFRIGERANT OIL AND APPROVED REFRIGERANT OILS .

Possible Deviation from Specification Possible Cause of Fault Corrective Action
  • High and low pressure normal at first After some time,
  • High pressure increases above specification,
  • Low pressure quickly drops to value in graph or below,
  • Required cooling output is no longer attained.
  • Actuation of A/C Compressor Regulator Valve -N280- malfunctioning.
  • Moisture in refrigerant circuit
-- Check the A/C Compressor Regulator Valve -N280- activation. Refer to Refrigerant Circuit .-- Clean the refrigerant circuit (flush with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blow through with compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN ).
  • High and low pressure normal at first
  • After lengthy driving time, low pressure drops excessively (evaporator ices up).
  -- Replace the receiver/dryer with dryer.-- Evacuate the refrigerant circuit for at least three hours.-- Charge the refrigerant circuit.-- Repeat the test.
 
  • A/C Compressor Regulator Valve -N280- faulty
-- Check the A/C Compressor Regulator Valve -N280- functionality. If necessary, replace the valve -N280- and check for dirt. Refer to A/C Compressor Regulator Valve -N280-, REMOVING AND INSTALLING .
NOTE:

It is not initially necessary to clean the refrigerant circuit (flush using refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A or blow through using compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN when this problem occurs since normally there is only a small quantity of moisture in the system which can be removed by lengthy evacuation.

If a problem involving moisture in refrigerant circuit only occurs after a lengthy operating period or only infrequently (low pressure drops below specification and evaporator ices up), it is sufficient to replace the dryer installed in receiver/dryer (adjust quantity of refrigerant oil). Refrigerant circuit is then to be evacuated for at least three hours.

With this malfunction, evaporator may ice up although the quantity of refrigerant in circuit is OK.

Problem with Evaporator Vent Temperature Sensor -G263- can also cause icing-up of refrigerant circuit. If this problem is encountered, also pay attention to measured value of Evaporator Vent Temperature Sensor -G263-. Use the Vehicle Diagnostic Tester ("OBD" or "Guided Fault Finding"  for the A/C System) and COOLING OUTPUT, CHECKING or Refrigerant Circuit .

Possible Deviation from Specification Possible Cause of Fault Corrective Action
  • High pressure normal
  • Low pressure too low (see graph)
  • The required cooling performance is obtained.
  • Actuation of A/C Compressor Regulator Valve -N280- malfunctioning.
-- Check the A/C Compressor Regulator Valve -N280- activation. Refer to Refrigerant Circuit .-- Clean refrigerant circuit (flush with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A or blow through with compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN (not always necessary, see notes).
 
  • A/C Compressor Regulator Valve -N280- faulty
-- Check the A/C Compressor Regulator Valve -N280- functionality. If necessary, replace the A/C Compressor Regulator Valve -N280- and check for dirt. Refer to A/C Compressor Regulator Valve -N280-, REMOVING AND INSTALLING .
 
  • Expansion valve or A/C compressor faulty.
  • A/C compressor faulty.
-- Replace the expansion valve and receiver/dryer-- Charge the refrigerant circuit.-- Repeat the test if the function is not OK:-- Replace the A/C compressor.-- Charge the refrigerant circuit.-- Repeat the test.
NOTE:

For the malfunction "high pressure normal, low pressure too low", note the following: With this malfunction, evaporator may ice up although the quantity of refrigerant in circuit is OK.

If the problem is with the -N280- A/C Compressor Regulator Valve (regulator valve is not actuated but A/C compressor operates nevertheless), refrigerant circuit does not have to be cleaned (flush with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blow through using compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN ). In this case, it is sufficient to replace the A/C compressor (observe quantity of refrigerant oil in A/C compressor).

If the expansion valve is malfunctioning (permanently closed or does not open sufficiently), the A/C Compressor Regulator Valve -N280- is actuated to maximum output and low pressure drops to value in graph or below (compressor draws off refrigerant from low-pressure side). As however refrigerant cannot flow via the expansion valve, the cooling output is not attained and high pressure may also not increase or only increase slightly due to the absence of energy conversion.

Check the measured values from the Evaporator Vent Temperature Sensor -G263- and the A/C Compressor Regulator Valve -N280- control. If the measured value from the Evaporator Vent Temperature Sensor -G263- is incorrect, the evaporator may ice up or cooling output is not attained. Use the Vehicle Diagnostic Tester ("OBD" or "Guided Fault Finding for the A/C System") and COOLING OUTPUT, CHECKING or.

Possible Deviation from Specification Possible Cause of Fault Corrective Action
  • High pressure normal or too high
  • Low pressure too high (see graph)
  • A/C compressor noise (particularly after switch-on)
  • The required cooling performance is obtained.
  • Actuation of A/C Compressor Regulator Valve -N280- malfunctioning.
  • Too much refrigerant in the circuit.
  • Expansion valve faulty
  • A/C compressor faulty.
-- Check the A/C Compressor Regulator Valve -N280- activation. Refer to Refrigerant Circuit .-- Extract refrigerant from the refrigerant circuit
  • If quantity of refrigerant extracted roughly corresponds to specified capacity:
-- Replace the expansion valve and receiver/dryer-- Charge the refrigerant circuit.-- Repeat the test if the function is not OK:-- Replace the A/C compressor.
  • If quantity of refrigerant extracted is substantially greater than specified capacity:
-- Charge the refrigerant circuit.-- Repeat the test.
NOTE:

This fault may also be caused by too much refrigerant oil in the circuit. Overfilling with refrigerant oil can occur if, for example, the compressor has been replaced without adjusting the quantity of refrigerant oil.

If the expansion valve is malfunctioning (permanently closed or does not open sufficiently), the A/C Compressor Regulator Valve -N280- is actuated to maximum output and low pressure drops to value in graph or below (compressor draws off refrigerant from low-pressure side). Since refrigerant cannot flow via expansion valve, cooling output is not attained, high pressure may also not increase or only increase slightly due to the absence of energy. Use the Vehicle Diagnostic Tester ("OBD" or "Guided Fault Finding for the A/C System") and COOLING OUTPUT, CHECKING or Refrigerant Circuit .

Possible Deviation from Specification Possible Cause of Fault Corrective Action
  • High and low pressure normal
  • The required cooling performance is obtained.
  • Actuation of A/C Compressor Regulator Valve -N280- malfunctioning.
  • Too much refrigerant in the circuit.
  • Expansion valve faulty
-- Check the A/C Compressor Regulator Valve -N280- activation. Refer to Refrigerant Circuit .-- Discharge the refrigerant circuit.-- Clean the refrigerant circuit (flush with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blow through with compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN ).
  • High and low pressure normal
  • A/C compressor noise (particularly after switch-on)
  • The required cooling performance is obtained.
  -- Fill in correct quantity of refrigerant oil into circuit (see note).-- Charge the refrigerant circuit.-- Repeat the test if the function is not OK:-- Replace the expansion valve.-- Charge the refrigerant circuit.-- Repeat the test.
NOTE:

Overfilling with refrigerant oil can occur if, for example, the compressor has been replaced without adjusting the quantity of refrigerant oil.

If expansion valve is malfunctioning (permanently open), evaporator temperature is no longer regulated such that only refrigerant in gaseous state exits from the evaporator. Under certain usage conditions, liquid droplets may then be drawn in by the compressor and cause noise (liquid cannot be compressed).

If there is too much refrigerant oil in the circuit, the compressor must be drained and the receiver/dryer must be replaced. After cleaning the refrigerant circuit (flushing with refrigerant R134a. Refer to REFRIGERANT CIRCUIT, CLEANING (FLUSHING) WITH REFRIGERANT R134A ; or blowing through using compressed air and nitrogen. Refer to REFRIGERANT CIRCUIT, FLUSHING WITH COMPRESSED AIR AND NITROGEN ), the correct quantity of refrigerant oil is filled into the circuit. Refer to REFRIGERANT R134A CAPACITIES, REFRIGERANT OIL AND APPROVED REFRIGERANT OILS .