Possible Deviation From Specified Value During The Pressure Test (9 Of 12)
| Possible Deviation from Specified Value During the Pressure Test |
|---|
|
| Possible causes for the deviation from specified value and their solutions |
|
| Final Procedures |
| -- Charge the refrigerant circuit. Refer to REFRIGERANT CIRCUIT, CHARGING .-- Repeat the test. Refer to ELECTRICALLY-DRIVEN A/C COMPRESSOR, CHECKING PRESSURE WITH A/C SYSTEM SWITCHED ON . |
For the malfunction "high pressure normal, low pressure too low", note the following: With this fault, it may be that the evaporator in the heater and A/C unit is icing up although the refrigerant quantity in the circuit is OK.
If there is a fault in the A/C compressor (the A/C compressor is activated by the A/C compressor control module at too high of a speed), it is not necessary to clean the refrigerant circuit by flushing with refrigerant R1234yf. In this case, it is sufficient to replace the A/C compressor (observe quantity of refrigerant oil in A/C compressor and if necessary adjust). Refer to REFRIGERANT CIRCUIT, CLEANING .
If the expansion valve for the evaporator for cooling the high-voltage components is faulty (or the function and activation is faulty) is always closed or does not open wide enough the A/C compressor is also activated with the maximum output (the required temperatures in the heat exchanger are not reached). The pressure on the low pressure side only then falls to the specified value or lower when at the same time the front heater and A/C unit no cooling output is needed. The A/C compressor extracts the refrigerant from the low pressure side from both evaporators. Because no refrigerant can low over the expansion valve in the front heater and A/C unit and the cooling output in the evaporator for cooling the high voltage battery is not reached (there is a malfunction in the area of the evaporator for the cooling of the high voltage battery) the electric A/C compressor is activated with a higher speed. If not refrigerant can flow the pressure on the low pressure side falls under the specified value, high pressure may also not increase or only increase slightly due to the absence of energy. The same applies if a valve in the refrigerant circuit is not OK a malfunction in the incorporation of the evaporator for cooling the high-voltage battery in the high-voltage system refrigerant circuit or the pump or a valve installed there is not OK. Then the High-Voltage Battery Heat Exchanger is cooled, but the cooled coolant reached the high-voltage battery heat exchanger which should not be cooled. Use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function. Refer to Coolant Circuit .
A malfunction on the Evaporator Vent Temperature Sensor -G263- or/and on the pressure/temperature sensor the can lead to this concern. Also pay attention to the measured values of the different pressure/temperature sensor in the refrigerant circuit. Use the Vehicle Diagnostic Tester in the"Guided Fault Finding" function. Refer to COOLING OUTPUT, CHECKING .
Refer to Possible Deviation From Specified Value During The Pressure Test (1 Of 12) for additional information.