Possible Deviation From Specified Value During The Pressure Test (11 Of 12)
| Possible Deviation from Specified Value during the Pressure Test |
|---|
|
| Possible causes for the deviation from specified value and their solutions |
|
| Final Procedures |
| -- Charge the refrigerant circuit. Refer to REFRIGERANT CIRCUIT, CHARGING .-- Repeat the test. Refer to ELECTRICALLY-DRIVEN A/C COMPRESSOR, CHECKING PRESSURE WITH A/C SYSTEM SWITCHED ON . |
Overfilling with refrigerant oil can occur if, for example, the compressor has been replaced without adjusting the quantity of refrigerant oil.
If for example the expansion valve for the evaporator in the heater and A/C unit or for the evaporator for cooling the high-voltage battery is faulty (always open) the evaporator temperature (in the heater and A/C unit) is no longer regulated that only refrigerant in gaseous state exits from the evaporator. Under certain usage conditions, liquid droplets may then be drawn in by the compressor and cause noise (liquid cannot be compressed).
If there is too much refrigerant oil in the circuit, the compressor must be drained and the receiver/dryer must be replaced. After cleaning the refrigerant circuit (flushing with refrigerant R1234yf) and fill it with the correct quantity of refrigerant oil in the circuit. Refer to REFRIGERANT CIRCUIT, CLEANING and Technical Data .
Refer to Possible Deviation From Specified Value During The Pressure Test (1 Of 12) for additional information.